Field tools · Calculator

External Static Pressure (ESP)

Drop your supply-side and return-side manometer readings, pick the installed coil / filter / heater section, and ChillFlow resolves the system ESP against the ACCA residential target of ≤ 0.50 inH₂O.

External Static Pressure (ESP)
US units · inH₂O
Enter the supply-side and return-side manometer readings, pick the installed coil / filter / heater, and ChillFlow resolves the system ESP against the ACCA residential target (≤ 0.50 inH₂O).

step ±0.05

step ±0.05

After commissioning / annual tune-up.

Standard efficiency — replace annually.

Heat-pump in cooling mode (no strip / gas).

ACCA / SMACNA residential — single-stage blower.

System ESP
0.90inH₂O

ESP high — outside residential band. Inspect coil / filter / duct for severe restriction.

  • Supply: 0.30 + Return: 0.30
  • Coil: 0.20 · Filter: 0.10 · Heat: 0.00
  • Total: 0.90 inH₂O
  • Residential target: ≤ 0.50 inH₂O ok · 0.50–0.80 high · ≥ 0.80 err · ≥ 1.00 critical
Optional — Rule-of-400 cross-check

step ±0.5

Enter system tonnage to surface the Rule-of-400 expected airflow and a matching friction-rate row from the reference table below.

Reference

Friction-loss reference

Typical hairpin friction rates — ACCA Manual D / SMACNA ballparks, not a substitute for system design.

SizeCFM (low–high)Friction (inH₂O/100 ft)Velocity (FPM)Notes
6"601200.12600Branch run-out, low CFM.
6"1212000.20900Branch run-out, design upper end.
8"901800.06500Branch run-out, typical.
8"1812800.10700Branch run-out, design mid.
8"2814000.18900Typical trunk transition.
10"1803200.06500Small trunk / branch.
10"3215000.09700Trunk mid.
12"3005000.04450Residential trunk, low end.
12"5018000.07650Residential trunk, typical.
12"80111000.10800Residential trunk, upper end.
14"5008000.04500Large trunk / lead duct.
14"80112000.06700Large trunk, design mid.
16"80012000.03500Lead / trunk, low end.
16"120116000.05700Lead / trunk, design mid.

Round and rectangular rows are for straight galvanized steel run-out / trunk. Flex duct runs fully extended (≥ 4 ft) — kinked or coiled flex roughly doubles the friction rate.

ESP bands follow ACCA Manual D / SMACNA residential targets. High-velocity systems use a tighter ≤ 0.20 inH₂O band. Verify against the OEM air-handler spec sheet before adjusting blower speed.